Engineering Guide

Commissioning an EtherCAT Servo in CODESYS: 7 Steps

From the ESI file to the first move: master, task cycle, Distributed Clocks, SoftMotion axis, scaling and the most common faults.

Scope

This content supports preliminary sizing and architecture decisions; it does not replace the selected product manual or machine risk assessment.

1. Install the ESI file in the device repository

The ESI (EtherCAT Slave Information) file tells the master the drive's process-data mapping, the modes it supports and its synchronisation settings. Download the file that matches the drive's full order code from the Document Centre and install it in the CODESYS Device Repository.

  • The drive revision and the ESI revision must match
  • Do not mix revisions of the same drive in a project

2. Add the EtherCAT Master and scan

Add an EtherCAT Master to the device tree and select the network interface the drives are connected to. A scan lists the devices in wiring order, and that order must match the physical one.

  • Wire from IN to OUT on every device
  • If a device is missing from the scan, check cables and ports first

3. Set the task and cycle time

Motion and EtherCAT communication must run in the highest-priority task with a fixed cycle, and that task must be selected as the bus cycle task. 1 ms is a good start for most servo applications; the task must finish every cycle without overrun.

  • Move machine logic and HMI communication to lower-priority tasks
  • Enable the task watchdog

4. Enable Distributed Clocks

In cyclic synchronous position mode (CSP), Distributed Clocks make every drive apply the command at the same instant. The SYNC0 period must equal the task cycle.

T_SYNC0 = T_task

5. SoftMotion axis and scaling

Create a SoftMotion axis for each drive. Scaling sets how many encoder counts one engineering unit (mm, degree) is worth. The typical sign of wrong scaling is an axis that goes the right way but the wrong distance.

  • Example: 17-bit encoder (131,072 counts/rev), 1:1, 10 mm pitch → 13,107.2 counts/mm
counts/unit = (counts/rev × gear ratio) / (units/rev)

6. First move: MC_Power, MC_Jog, MC_Home

Power the axis with MC_Power first, confirm direction and limits at low speed with MC_Jog, then reference it with MC_Home. Watch every block's Error and ErrorID outputs.

  • Do the first jog with a low torque limit
  • Test hardware limits before software limits

7. The most common faults

If a slave stays in PRE-OP or SAFE-OP, the AL Status Code gives the reason: usually an ESI mismatch, the PDO mapping or the DC settings. Working-counter errors are almost always a cable, connector or shielding problem.

SymptomLikely causeFirst check
Slave stays in PRE-OP ESI / firmware mismatch AL Status Code and revision
Will not go from SAFE-OP to OP DC / SYNC0 settings, watchdog SYNC0 = task cycle
Working-counter error Cable, connector, noise Per-port error counters
Axis goes the wrong distance Scaling Counts-per-unit calculation

Frequently asked questions

Should Distributed Clocks always be on?

In cyclic synchronous position mode and coordinated multi-axis motion, yes. For independent axes in profile position mode it is not required.

How do I choose the cycle time?

By the shortest period in which the task always completes; start at 1 ms, shorten if needed, and watch the overrun counter.

Technical sources

Sources are publications from standards owners and manufacturers.